How many amps does a 60 hp motor draw?

How many amps is a 60 hp motor?

Here are the Full Load Amp (FLA) values for typical 230VAC and 480VAC 3 phase motors.

Motor horsepower Full load amps 230VAC Full load amps 460VAC
60 149 75
75 180 90
100 245 123
125 310 155

What size breaker do I need for a 50 hp motor?

Full-Load Current and Circuit Protection Data for Three-Phase AC Motors

Motor Horsepower Breaker Size
40 230 V 460 V 175 100
50 230 V 460 V 200 150
60 230 V 460 V 250 200
75 230 V 460 V 300 200

How do I convert HP to amps?

How to Convert Horsepower to Amps

  1. Amps = (Horsepower × 746) ÷ Efficiency ÷ Volts.
  2. Watts = Horsepower × 746.
  3. Watts = Wattsη
  4. Amps = Watts ÷ Volts.
  5. Amps = HP × 746V × η × PF.

How many amps does a hp motor draw?

AMP DRAW BASED ON HORSEPOWER

HP 1 Phase Amps 3 Phase Amps
115 volt 230 volt
1 16 4.2
1-1/2 20 6
2 24 6.8
IT IS INTERESTING:  Where is the VIN on the windshield?

How many amps does a .5 HP motor draw?

Example: A 5 HP motor at 230V, 3PH is12. 4 amps.

How many amps does a 40 hp motor draw?

AC Motor Full Load Amperes

HP 200 Volts 220-240 Volts
40 120 104
50 150 130
60 177 154
75 221 192

What wire do I use for 40 amps?

For a maximum of 40 amps, you’ll need a wire gauge of 8. Many electric cooking appliances require 40 amps such as electric cooktops.

How many amps does a 7.5 hp motor draw at 480 volts?

AC Motor Full Load Amperes

HP 200 Volts 440-480 Volts
5 17.5 7.6
7.5 25.3 11
10 32.2 14
15 48.3 21

How many amps does a 10hp single phase motor draw?

Full-Load Current in Amperes Single-Phase Alternating Current Motors

HP 115V 230V
5 56 28
7-1/2 80 40
10 100 50
The voltages listed are rated motor voltages. The listed currents are for system voltage ranges of 110 to 120 and 220 to 240.

How many amps does a 1.5 HP 220v motor draw?

The 1.5 HP Baldor motor that turns at 1725 will draw 18 amps according to its name plate.

How many HP is a 3 amp motor?

Common Amps to Horsepower Conversions

Amps Horsepower Voltage
3 A .43 HP 120 V
4 A .58 HP 120 V
5 A .72 HP 120 V
6 A .87 HP 120 V

How many amps does a 30 kW motor draw?

Three Phase Motors

MOTOR RATING HP APPROX. F.L.C. AT LINE VOLTAGE
22 kW 30 74
30 kW 40 99
37 kW 50 130
45 kW 60 147

How much current does a motor draw?

Calculate the amps used by dividing the wattage by the voltage. For example a 500-watt motor — running on 50 volts — will draw 10 amps. A motor with the same wattage — running on 20 volts — will use 25 amps. This is the theoretical number of amps used by the motor.